ENCS-3m...-1(2)
|
ENCS-3m...-3
|
ENCS-3m...-4(5)
|
Interfaces
|
6(8) × RS‑485, 4(2) × RS‑232,
2 × 100Base‑TX,
USB (option G, GT), CAN
|
8 × RS‑485, 2 × RS‑232,
4 × 100Base‑TX (PRP, RSTP), USB
|
8 × RS‑485, 2 × RS‑232,
2 × 100Base‑TX,
2 × 100Base‑FX LC SM or
2 × 100Base‑FX LC MM (PRP, RSTP), USB
|
Cellular
|
UMTS/HSPA+,
GSM/GPRS/EDGE (option G)
|
n/a
|
n/a
|
Built-in
GPS-receiver
|
available (option GT)
|
n/a
|
n/a
|
Data polling
|
up to 240 devices;
up to 8192 measurement values, 4096 digital signals, 2048 commands;
IEC 61850-8-1 (MMS, GOOSE), IEC 60870‑5‑101/103/104, Modbus RTU, Modbus TCP, SNMP;
ENIP‑2, ENMV‑1, EMAX/TMAX, Sepam
|
Outgoing connection
|
up to 16 connections Ethernet and 3G/2G:
IEC 60870‑5‑104, IEC 61850 (MMS, GOOSE), Modbus TCP, SNMP
|
up to 16 connections Ethernet:
IEC 60870‑5‑104,
IEC 61850 (MMS, GOOSE), Modbus TCP, SNMP
|
up to 16 connections Ethernet:
IEC 60870‑5‑104,
IEC 61850 (MMS, GOOSE), Modbus TCP, SNMP
|
|
up to 10 connections RS‑485, RS-232:
IEC 60870‑5‑101,
Modbus RTU
|
up to 10 connections RS‑485, RS-232:
IEC 60870‑5‑101, Modbus RTU
|
Additional features
|
manual entry, substituting and blocking data; logical expressions executing
|
Event logging
|
status of digital inputs and outputs, diagnostic messages; software upgrade, configuration update, power supply events
|
Time sync
|
according to IEC 60870‑5‑101, IEC 60870‑5‑104, SNTP (client and server)
|
Programmed logic
|
logical functions: AND, OR, XOR, CMP, RS FF, TIMER
|
Power supply
|
18...36 VDC, 42...176 VDC, 120...370 VDC or 100...265 VAC (45...55 Hz), 10 VA
|
18...36 VDC, 40...160 VDC, 120...370 VDC or 100...265 VAC (45...55 Hz), 10 VA
|
18...36 VDC, 40...160 VDC, 120...370 VDC or 100...265 VAC (45...55 Hz), 10 VA
|
Operating conditions
|
–40...+70 °С
|
"
|
"
|
Design
|
75 × 100 × 110 mm, DIN‑rail mounting, IP40
|