ECIT is a combined single-phase instrumental transformer for medium-voltage switchgear enclosure. ECIT scales current and voltage signals to small, digitalizes and measures them (including with an aperiodic component), and publishes current and voltage values via digital interfaces as a sampled values (SV) to the ethernet network (Process Bus) in accordance with IEC 61869-9.

Unlimited number of devices such as digital relay protection terminals, digital electricity meters, electricity quality control systems etc., which are connected to the process bus, are receiving multicast messages published by ECIT and used them instead of real analog current and voltage signals for measurement, protection and other purpose.

Furthermore, ECIT supports fault recorder function and writes current and voltage waveforms into COMTRADE files with sampling rate up to 14.4 kHz.

Metrological characteristics

Rated voltage (Upr)

3000/√3...11000/√3 В

for measurement (0,2·Upr ≤ U ≤ 1,2·Upr)

accuracy class — 0.5 (IEC 60044-7); ratio error — 0,5%, phase displacement — 20 min

for protection (0,005·Upr ≤ U ≤ 1,9 Upr)

accuracy rating — 3P (IEC 60044-7); ratio error — 3%, phase displacement — 120 min

Primary rated (extended) current (Ipr)

100 (1250) А

for measurements (0,01·Ipr ≤ I ≤ 12,5·Ipr)

accuracy rating — 0.5S (IEC 60044-8); ratio error — 0,75 (0,01·Ipr ≤ I < 0,05·Ipr), 0,5 (0,5·Ipr ≤ I ≤ 12,5·Ipr), phase displacement — 45 min (0,01·Ipr ≤ I < 0,05·Ipr), 30 min (0,5·Ipr ≤ I ≤ 12,5·Ipr)

for protection (Ipr≤ I ≤ 200·Ipr)

accuracy rating — 5P (IEC 60044-8); ratio error — 1%, composite error — 5%, phase displacement — 60 min

Other information

Sampling rate

4000, 4800, 12000, 14400 (max — 96000) Hz

Interfaces

2 × 100Base-TX, PRP, RSTP

Communication protocols

IEC 61850-9-2 (SV80, SV96, SV288), C37.118.2 (400 fps), IEC 60870-5-104, PTPv2

Ambient operating conditions

–45...+50 °С, RH — up to 98 % (+25 °С), 84…106,7 kPa (630…800 mm Hg)

Place of use

Indoor areas up to 1,000 m above mean sea level

Power supply

18...36 V DC, 10 W

Design

270 × 136 × 113 mm, 3.6 kg, IP30