ENIP-2 Panel is panel device with TFT touch screen, 480 × 272. Current and voltage measurement inputs, power circuits and two interfaces are located on the rear.
ENIP-2 Panel supports standard communication protocols.
Display modes are controlled by touch screen and buttons. ENMV-1 external modules can serve as extensions for digital input and output.
Measurements |
rated current: 1 or 5 А, rated voltage: 57.7 (100), 230 (400) V, 400 (690) V |
Voltage (input range: 20–150 %) |
±0.2 % |
Current (input range: 1–200 %) |
±0.2 % |
Power (active/reactive/apparent) |
±0.5 % |
Frequency |
±10 mHz |
Measuring time / update settings |
50 msec (sliding window) / 20 msec |
Additional parameters |
cos, tg, angles (phase and average), active and reactive energy |
Input/output |
digital inputs/outputs (up to 4 modules): |
Event logging |
I/O history, event log |
Interfaces and protocols |
1 or 2 × RS‑485 (600...115200 baud): IEC 60870‑5‑101, Modbus RTU; USB; 1 × 100Base‑TX: IEC 60870‑5‑104, IEC 60870‑5‑101 (UDP), Modbus TCP, Modbus RTU, SNMP |
Real-time clock |
500 µs (error less than 5 s per day without sync); time sync on RS‑485 according IEC 60870‑5‑101 |
Power supply |
18...36 VDC, 100...265 VAC (45...55 Hz) or 120...370 VDC, 10 VA |
Operating conditions and design |
from –40 up +70 °C (screen from −20 up +70 °С), |