ENIP-2 Panel

ENIP-2 Panel is panel device with TFT touch screen, 480 × 272. Current and voltage measurement inputs, power circuits and two interfaces are located on the rear.

ENIP-2 Panel supports standard communication protocols.

Display modes are controlled by touch screen and buttons. ENMV-1 external modules can serve as extensions for digital input and output.

Measurements

rated current: 1 or 5 А, rated voltage: 57.7 (100), 230 (400) V, 400 (690) V

Voltage (input range: 20–150 %)

±0.2 %

Current (input range: 1–200 %)

±0.2 %

Power (active/reactive/apparent)

±0.5 %

Frequency

±10 mHz

Measuring time / update settings

50 msec (sliding window) / 20 msec

Additional parameters

cos, tg, angles (phase and average), active and reactive energy

Input/output

digital inputs/outputs (up to 4 modules):
ENMV‑1‑6/3R, ENMV‑1‑24/0, ENMV‑1‑0/22, ENMV‑1‑0/20, ENMV‑1‑16/6, ENMV‑1‑16/3R,
programmable logic (up to 32 with 32 functions: AND, OR, CMP, TIMER, VALID

Event logging

I/O history, event log

Interfaces and protocols

1 or 2 × RS‑485 (600...115200 baud): IEC 60870‑5‑101, Modbus RTU; USB;

1 × 100Base‑TX: IEC 60870‑5‑104, IEC 60870‑5‑101 (UDP), Modbus TCP, Modbus RTU, SNMP

Real-time clock

500 µs (error less than 5 s per day without sync);

time sync on RS‑485 according IEC 60870‑5‑101

Power supply

18...36 VDC, 100...265 VAC (45...55 Hz) or 120...370 VDC, 10 VA

Operating conditions and design

from –40 up +70 °C (screen from −20 up +70 °С),
120 × 120 × 49 mm (IP40 front panel, IP30 housing)