ESX231

The ESX231 series includes compact I/O modules for digital and analog signals. ESX231 can be used as independent components of a distributed automated control system or as cost-effective additional modules for ENIP-2 and ESM measuring devices.

RS-485 port is divided into two RJ45 sockets with pinout (interface + power supply) similar to ENIP-2 (RS-485-2) and ESM (COM-2). Patch cords can be used to connect ESX231 devices.

ENIP-2 and ESM internal power supply allows powering up to three ESX231 modules or one ESX231 module with ENMI. The communication line between ENIP-2 (ESM) and powered devices should be up to 20 meters. If it is necessary to connect a larger number of ESX231 modules or the line length exceeds 20 m, external power must be provided — for example, using the EX5RJX splitter.


Buy
Buy
Buy
Buy


ESX231-8/0

ESX231-0/4R

ESX231-1X/0

ESX231-0/1P

Number of digital inputs (DI)

dry/wet contacts: 24/110/220 VDC

8

-

-

-

Number of digital outputs (DO EMR)

250 VAC 6 F, 250 VDC 0.2 A, 30 VDC 6 A

-

4

-

-

Number of analog inputs (AI)

±12 V, ±200 mV, ±75 mV, ±20 mA, ±5 mA

-

-

1

-

Number of analog outputs (AOP)

4...20 mA, 0…5(20,24) mA, ±5(20,24) mA

-

-

-

1

Interfaces


Exchange protocols

1 × RS‑485: Modbus RTU, IEC 60870‑5‑101

Power supply

22...26 VDC, 2 W

22...26 VDC, 2 W

22...26 VDC, 2 W

22...26 VDC, 3 W

Operating temperature

−40...+70 °С

Housing, mm

57 × 113 × 42

57 × 113 × 56

34 × 113 × 42

34 × 113 × 42

Mounting

DIN-rail mounting

Where to get more information about your products?

Write to us: sales@ens.ru