ECIT-1s
|
Modification |
ECIT-1s-15 |
ECIT-1s-35 |
|
Voltage Class |
up to 15 kV |
up to 35 kV |
|
Rated primary current, In |
50 A |
50 A |
|
Current accuracy class |
0.5S/5PR500 |
0.5S/5PR400 |
|
Rated primary current up to |
1250 А |
1250 А |
|
Rated short-time thermal current, Ith |
25 kA/1 s |
25 kA/1 s |
|
Rated dynamic current, Idyn |
63 kA |
63 kA |
|
Rated primary voltage, Upr, |
(3...16)/√3 kV, 0.5/3P |
(6...36)/√3 kV, 0.5/3P |
|
Rated primary voltage up to, Um |
17.5 kV |
40.5 kV |
|
Rated lighting impulse withstand voltage |
95 kV |
190 kV |
|
Rated short-duration power frequency withstand voltage (1 min) |
38 kV |
80 kV |
|
Design dimensions, mm weight, kg |
284 × 190 × 443 ≤ 10 |
410 × 190 × 592 ≤ 14 |
|
Sampling rate, Hz |
14400, 12000 |
|
|
Interfaces |
2 × 100Base‑TX (FX LC MM), RSTP, IEC 62439-3 PRP |
|
|
Protocols |
IEC 61850-9-2: 2 × SV (4800, 14400 fps), optional SP (50...4800 fps), |
|
|
Binary output |
140 VAC 0.46 A, 30 VDC 1 A, switching time 5 ms |
|
|
Time sync |
PTPv2 (IEC 61850-9-3), IRIG-A (RS-485) |
|
|
Disturbance recording |
10 records (1+4 s), sampling rate 2400 or 2000 Hz |
|
|
Relay protection |
PVOC, PIOC |
|
|
Optional |
Extended protection and automation suite: PVOC/PDOC, PIOC, SARC, PTEF/PDEF, PTUV, PPBR, RBRF, Busbar Blocking logic, Dead/Live line detection Publication SP, merging SP Three-phase energy metering |
|
|
Power supply |
18...36 VDC, 10 W |
|
|
Operating conditions |
-60(-70)…+50(+60) °С, RH — up to 100 % (+25 °С), 84…106.7 kPa, 1000 m above sea level |
|